RFQ - 12.5-Ton Gas/Electric Rooftop Unit Package
DEPT OF DEFENSE › DEPT OF THE ARMY › W6QM MICC-FT DRUM
Description
This requirement is for a complete, like-for-like replacement of an existing commercial rooftop unit, or RTU. The required equipment package must meet or exceed the following specifications. The base unit must be one 12.5-Ton Gas Heat and Electric Cooling Rooftop Unit with a 208-volt, 3-phase power supply. The unit must have single circuit, two-stage cooling with a minimum 10.8 EER or 15.0 IEER, and two-stage medium gas heat with a first stage of 180 MBH input and a second stage of 224 MBH input. It must also feature a high-static direct-drive vane axial fan, such as a Carrier EcoBlue or equivalent, and use a modern, low GWP refrigerant like R-454b. The package must also include the following compatible accessories: one Vertical Economizer with a controller, one Enthalpy sensor and harness for the economizer, and one standalone, two-stage programmable thermostat.
More active opportunities in NAICS 423730
| Title | Agency | Type | NAICS | Posted | Deadline |
|---|---|---|---|---|---|
| Air Filters | DEPT OF THE ARMY | Solicitation | 423730 | Jul 14, 2026 | Jul 24, 2026(8d) |
| Spot Cooler Parts | DEPT OF THE ARMY | Combined Synopsis/Solicitation | 423730 | Jul 13, 2026 | Jul 20, 2026(4d) |
| ALASKA TWO POINT FIVE TON ENVIRONMENTAL CONTROL UNIT | DEPT OF THE ARMY | Combined Synopsis/Solicitation | 423730 | Jul 9, 2026 | Jul 20, 2026(4d) |
| HVAC Air Filters | STATE, DEPARTMENT OF | Solicitation | 423730 | Jul 9, 2026 | Jul 24, 2026(8d) |
| FCI GILMER - CHILLER MOTOR & VFD PARTS | FEDERAL PRISON SYSTEM / BUREAU OF PRISONS | Award Notice | 423730 | Jul 8, 2026 | — |