4310--Replacement Medical Air Equipment Grand Junction, CO

VETERANS AFFAIRS, DEPARTMENT OF › VETERANS AFFAIRS, DEPARTMENT OF › NETWORK CONTRACT OFFICE 19 (36C259)

Solicitation #
36C25926Q0523
Posted
Jul 15, 2026
Response deadline
Jul 22, 2026(7d)
Archive date
Aug 6, 2026
NAICS
PSC
4310
Place of performance
Grand Junction, 81501
Contact
Stephanie Cahill · [email protected]

Description

Amendment 001 to Solicitation #36C25926Q0523 (Replacement Medical Air Equipment) This amendment s purpose is to list and answer the questions submitted by the questions deadline as specified in the solicitation. Questions and Answers: Desiccant Dryer / Medical Air Load Calculation: The scope states that the desiccant air dryer shall be sized for the calculated system demand. Can the Government provide the existing or required medical air load calculation? Also, please confirm the required dryer dew point, or whether the system should be sized to the standard NFPA 99 medical air dew point requirement. No, you will have to do the calculations. See Plumbing PG-18-10 paragraph 8.2.3.2(k). Seismic Certification The solicitation specifically identifies OSHPD Seismic Certification for the medical vacuum pump system. Please confirm whether OSHPD Seismic Certification is also required for the medical air compressor system. No, it is not. Site Access / Rigging / Equipment Placement Can the Government provide any available photos, drawings, or layout information for the mechanical room and the equipment delivery path? Specifically, we are requesting door widths, corridor widths, elevator information if applicable, and any known rigging or access limitations. Please also confirm whether the new equipment is expected to be installed in the same footprint/location as the existing equipment. As available, however we request that you complete a site survey. Existing Piping and Electrical Tie-Ins Can the Government provide any available as-built drawings, photos, or additional information showing the existing medical air and medical vacuum piping connection points, electrical panels, disconnects, and tie-in locations? As available, however we request that you complete a site survey. Alarm Panel Compatibility Please provide the make and model of the existing area alarm panels and master alarm panels that the new equipment will need to communicate with. **Pending additional information** Award / Start Timeline: The solicitation states that the period of performance shall not exceed 120 days from award. Is there an anticipated award date or estimated project start timeframe that offerors should use for planning and equipment lead time purposes? Once quotes are received, it is anticipated that an award would be made within a few weeks. However, no set dates can be provided. Upon receipt of award, the vendor would be expected to attend a post-award meeting to discuss logistics and a more firm timeline. Offerors should include in their quote package their anticipated delivery lead times as well as an estimate of how long the installation and verification process would take once equipment is onsite. Relative Humidity of installation area? The mech room is around 25%, but this varies. Grand Junction, CO Relative Humidity Profile Annual Average Relative Humidity: Approximately 40 50%.

Monthly Variation: Winter (Dec-Feb): Highest (average 60 65% in early morning, ~35 40% in afternoon) Summer (June-Aug): Lowest (average 30 35% in early morning, ~15 20% in afternoon) Afternoon Minimums (most relevant for HVAC/medical air calculations): Can drop to 10 20% in summer afternoons. Source: NOAA climate data; met expectations for high desert/mountain valley climates.

Summary Table: Month Early AM (%) Afternoon (%) January 55 65 35 40 April 50 55 25 30 July 35 40 15 20 October 45 50 30 35 If you need precise humidity values for load calculations, HVAC design, or medical air dryer sizing: Use 20% RH (afternoon summer) for worst-case scenario standards. Max Room temperature? Mid to late 80 s.

View on SAM.gov (attachments & response) ↗

More active opportunities in NAICS 333912

TitleAgencyTypeNAICSPostedDeadline
43--FEED,AIR COMPRESSORDEFENSE LOGISTICS AGENCYCombined Synopsis/Solicitation333912Jul 15, 2026Jul 27, 2026(11d)
Quincy Brand Name or Equal Oil-Free Rotary Scroll Dental Air CompressorVETERANS AFFAIRS, DEPARTMENT OFPresolicitation333912Jul 15, 2026Jul 24, 2026(8d)
43--FEED,AIR COMPRESSORDEFENSE LOGISTICS AGENCYAward Notice333912Jul 15, 2026
4320-012698849, seal assembly, shaftDEFENSE LOGISTICS AGENCYPresolicitation333912Jul 15, 2026Aug 28, 2026(44d)
43--HOOD ASSEMBLY FIBERDEFENSE LOGISTICS AGENCYAward Notice333912Jul 15, 2026
4310--Replacement Medical Air Equipment Grand Junction, CO · FedQuery