Correct Electrical Deficiencies
VETERANS AFFAIRS, DEPARTMENT OF › VETERANS AFFAIRS, DEPARTMENT OF › 246-NETWORK CONTRACTING OFFICE 6 (36C246)
Description
SOW 565-22-500 Correct Electrical Deficiencies Fayetteville VAMC Intent The project consists of correcting electrical deficiencies as noted from previous VA facility assessments. Improvements include; New electrical entrance building, medium voltage loop replacement, replace electrical distribution equipment, ground conductor corrections, incidental electrical equipment cleanup throughout the Fayetteville VAMC, and minor HVAC and Plumbing improvements. Period of performance 1,174 calendar days. Medium Voltage VA owned medium voltage loop and entrance equipment will be modified or replaced with the following scope: Replace existing medium voltage entrance equipment with new at campus entrance. Provide new building: Slab on grade, brick on CMU wall, Slate roof tile (to match existing facility) Provide new VA owned medium voltage cables in concrete encased duct bank for medium voltage loop. Approximately 300 . Demo and remove old VA owned medium voltage entrance metal shack. Replace medium voltage sectionalized switch. Provide new metal-clad switchgear with draw-out vacuum circuit breakers. Replace medium voltage oil filled transformer (1) Panel Replacement and Branch Circuit Improvements Correct deficiencies to electrical panels and branch circuit wiring which are not correctly sized, protected, or are at end of useful life, as identified through various inspections over the years. o All work will be phased. All replacements to existing equipment will require the contractor to filled-out a phasing plan for VA approval. All replacements to existing equipment will require a temporary power solution to minimize electrical outage to existing areas. Such deficiencies include: Replace-in-same-room building entrance and large distribution equipment: Normal (service entrance)
Switchboards: approx. 2 Generator switchboards: approx. 2 Automatic transfer switch: approx. 7 Replace-in-place distribution panels and panelboards distribution equipment Distribution Panels: approx. 5
Panelboards: approx. 68 Replace undersized feeders Redundant Gound Provide redundant equipment grounding conductor to a portion of the facility. Approx. 100,000 square feet of existing electrical branch circuit distribution in occupied space. HVAC And Plumbing Reroute (vertically & horizontally) Sewer piping and hot water piping to avoid electrical room. Provide exhaust fan to new Medium Voltage building. Incidental Electrical Equipment Cleanup Provide Identification tag to new and existing equipment throughout the facility: approx. 100 tags Clean debris from existing electrical enclosures throughout the facility: approx. 30 enclosures. Correct panel grounding, terminate cable directly to existing panel s ground bar: approx. 30 panels. ALTERNATE NO.1: BASE BID except delete Bldg 1, Floor 1 and Floor 3 of deficiency item 134 which directs the contractor to provide ground conductors in existing conduit. Which is noted on Sheet B01-E200.
More active opportunities in NAICS 236220
- Wilson Hall Floor 16 Electric and Elevator Machine Rooms Fire Rating and Mechanical Upgrade
- Deadline
- Dec 9, 2026(27d)
- Agency
- ENERGY, DEPARTMENT OF
- Type
- Solicitation
- NAICS
- 236220
- Posted
- Nov 11, 2026
- SABER V Hill AFB
- Deadline
- Nov 16, 2026(4d)
- Agency
- DEPT OF THE AIR FORCE
- Type
- Solicitation
- NAICS
- 236220
- Posted
- Nov 11, 2026
- ACC003 Weapons Generation Complex and Northern Flightline
- Deadline
- Nov 24, 2026(12d)
- Agency
- DEPT OF THE ARMY
- Type
- Solicitation
- NAICS
- 236220
- Posted
- Nov 10, 2026
- Z--CA-HUMBOLDT BAY NWR-TIDE GATE REPAIR
- Deadline
- Nov 13, 2026(1d)
- Agency
- DEPARTMENTAL OFFICES
- Type
- Presolicitation
- NAICS
- 236220
- Posted
- Nov 10, 2026
- Amendment 0006 to Provide Official RFI Responses, Update Solicitation Documents, Extend Proposal Due Date, & other Official Information
- Deadline
- Nov 25, 2026(13d)
- Agency
- VETERANS AFFAIRS, DEPARTMENT OF
- Type
- Solicitation
- NAICS
- 236220
- Posted
- Nov 10, 2026
| Title | Agency | Type | NAICS | Posted | Deadline |
|---|---|---|---|---|---|
| Wilson Hall Floor 16 Electric and Elevator Machine Rooms Fire Rating and Mechanical Upgrade | ENERGY, DEPARTMENT OF | Solicitation | 236220 | Nov 11, 2026 | Dec 9, 2026(27d) |
| SABER V Hill AFB | DEPT OF THE AIR FORCE | Solicitation | 236220 | Nov 11, 2026 | Nov 16, 2026(4d) |
| ACC003 Weapons Generation Complex and Northern Flightline | DEPT OF THE ARMY | Solicitation | 236220 | Nov 10, 2026 | Nov 24, 2026(12d) |
| Z--CA-HUMBOLDT BAY NWR-TIDE GATE REPAIR | DEPARTMENTAL OFFICES | Presolicitation | 236220 | Nov 10, 2026 | Nov 13, 2026(1d) |
| Amendment 0006 to Provide Official RFI Responses, Update Solicitation Documents, Extend Proposal Due Date, & other Official Information | VETERANS AFFAIRS, DEPARTMENT OF | Solicitation | 236220 | Nov 10, 2026 | Nov 25, 2026(13d) |